APC; Smart-UPS 2200VA; User Manual; APC Smart-UPS 2200VA SUA2200I User Manual. Product codes. Download Like. Full screen Standard. Page of 16 Go. Smart-UPS 2200/3000 VA 100/120/230 Vac Tower User Manual. All LEDs are off and the UPS is plugged into a wall outlet. Read and download APC Battery Charger Smart UPS 2200 VA User's Manual online. Download free APC user manuals, owners manuals, instructions, warranties and installation guides, etc.
Initial
To obtain warranty coverage, please fill out and return the warranty registration card now.
Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.
Placement
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Do not operate the UPS where the temperature and humidity is outside the specified limits.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.
Installation
To install this UPS, please follow the installation instructions in the
This UPS is equipped with a SmartSlot for accessories. See the APC Website (www.apcc.com) for available accessories.
Charge the battery
The UPS charges its battery whenever it is connected to utility power. The battery will charge fully during the first 4 hours of normal operation. Do not expect full runtime during this initial charge period.
Operating Instructions
Switch On — Switch Off
With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The
loads are immediately powered while the UPS performs a
Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS as a master on/off switch for the protected equipment.
Note: Whenever the UPS is plugged in and utility voltage is present, the charger maintains battery charge.
The
The UPS performs a
During the
If the UPS fails the
The loads are not affected by a failed test. Recharge the battery overnight and perform the
SmartTrim
The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage.
SmartBoost
The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage.
APC
Uninterruptible Power Supply
230 VAC User’s Manual
Rear Views
2200 and 3000 VA | 1000 and 1400 VA | 450 and 700 VA |
Connect Computer Interface Port (Optional)
Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the
Connect Ground Leads to TVSS Connector (Optional)
Apc Smart Ups 2200 Service Manual
The UPS features a TVSS connector for connecting the ground lead on transient voltage
Battery Pack Connector (3000 VA only)
Use the battery pack connector to connect the optional external battery pack.
On Battery
During
Low Battery
When the UPS is operating
100% | Battery Charge Bar Graph |
80% | The |
60% | shows the present charge of the UPS’s battery as a |
percentage of the battery’s capacity. When all five | |
40% | |
LEDs light, the battery is fully charged. The top | |
20% | LED goes out whenever the battery is not 100% |
charged. When the LEDs are flashing, the battery |
can supply less than the “low battery warning interval” time for the load.
Shutdown Mode
If there is no utility power present, a host system connected to the computer interface port can command the UPS to shut down. This is normally done to preserve battery capacity after a controlled shutdown of the protected system. In shutdown mode the UPS stops supplying power to the load, waiting for the return of utility power.
The UPS scrolls the front panel indicators sequentially in shutdown mode. If the UPS has shutdown due to a low battery, the UPS lights the Battery Charge Bar Graph only. When line power is restored, the UPS returns to
Replace Battery
If the battery fails a
85% | Load Bar Graph |
67% | The |
50% | shows the power drawn from the UPS by the load. |
The display indicates the percentage of the UPS’s | |
33% | |
rated capacity. For example, if three LEDs are lit, the | |
17% | |
load is drawing between 50% and 67% of the UPS’s | |
capacity. If all five LEDs light, thoroughly test your | |
complete system to make sure that the UPS will not | |
become overloaded. |
Voltage Sensitivity
The UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as distortions caused by operation with inexpensive
To reduce UPS sensitivity, press the configuration button on the rear panel. Use a pointed object such as a pen to press the button. Press it once to set the UPS’s sensitivity toreduced. Press it again to set the sensitivity tolow. Press the button a third time to
reset normal sensitivity.
normal
reduced | When the UPS is set to normal sensitivity, the |
configuration LED is brightly lit. When it is set to | |
low | |
reduced sensitivity, the LED is dimly lit. When it is | |
set to low sensitivity, the LED is off. |
•Press and hold the on/test button until the UPS begins beeping.
•Release the on/test button during the beeping to start the UPS.
Utility Voltage Bar Graph
196 | If no LEDs come on and the UPS is plugged into a | |
working AC power outlet, the line voltage is extremely | ||
264 | ||
low. If all five LEDs come on, the line voltage is | ||
extremely high and should be checked by an electrician. | ||
The display indicates that the voltage is between the | ||
247 | displayed value from the list and the next higher value. | |
230 | For example, with three LEDs lit, the input voltage is | |
213 | between 230 and 247 VAC. |
Note: The UPS starts a
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least 4 hours. Disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.
Extended storage
•At
•At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every 3 months.
Apc Smart Ups Rt 2200 Manual Pdf
Replacing the Battery
This UPS has an easy to replace
Note: Please read the cautions in the APC Safety Guide.
Once the battery is disconnected, the loads are not protected from power outages.
Battery Replacement Procedure - 2200 - 3000 VA Models
1. Grasp the top edge of the bottom front cover and tilt it out.
2.Unhook the bottom section of the front cover from the chassis and set it aside.
3.Use a
open the door.
4. Grip the wires for the front set of batteries and pull firmly to disconnect the connector from the battery compartment. Remove the batteries.
5.Pull the white cord on the front battery connector to remove the batteries.
6.Set aside the foam spacer located between the batteries.
7.Reach into the battery compartment and grasp the white cord on the other battery connector. Pull firmly to disconnect the connector and remove the second set of
batteries.
Note: Be careful removing the batteries - they are heavy.
8.Slide the first set of new batteries into the unit. Hold the connector down below the top of the batteries and toward the door, otherwise the assembly will not fit. Guide the connector over the top of the batteries and press firmly to connect it to the rear connector of the battery compartment.
9.Set the foam spacer against the rear batteries to prevent the wires from being pinched.
Note: Small sparks at the battery connectors are normal during connection.
10.Slide the second set of batteries in, then guide the connector over the batteries and press firmly to connect it to the front connector of the battery compartment.
11.Now close the battery door, replace the screws, and replace the lower front cover.
12.Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
Battery Replacement Procedure - 450 - 1400 VA Models
1. Grasp the top of the front cover and tilt it out and down.
2.Unhook the bottom of the cover from the chassis and lift it upward to expose the battery door. Be careful not to strain the ribbon cable. Do not touch the exposed
printed circuit board.
3. Fold the front cover on top of the UPS as shown.
4. Use a
Grasp the tab and gently pull the battery out of the UPS. 5. Disconnect the battery leads.
•For the 450 through 1000 VA models, loosen the connectors by gently wiggling them while pulling straight back from the battery connector.
• For the 1400 VA model, pull the two gray couplers apart to disconnect the battery.
6. Connect the battery leads to the new battery.
1400 VA | Note: Small sparks at the battery connectors are normal during connection. |
• For the 450 through 1000 VA models, connect the red wire to the positive (+) | |
terminal and the black wire to the negative | |
450 - 1000 VA | • For the 1400 VA model, connect the gray battery coupler to the UPS’s coupler. |
7. Now slide the battery into the UPS,close the battery door,replace the battery |
compartment screws, and replace the front cover.
8. Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
Place | Date | Stephen A. Lee, Regulatory Compliance Engineer | ||
Galway, Ireland | 1/1/97 | |||
Place | Date | |||
Gerard | Rutten, Managing Director, Europe |
User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory | User Selectable Choices | Description |
Default | |||
Automatic | Every 14 days | Every 7 days (168 hours), | Sets the interval at which the UPS |
(336 hours) | On Startup Only, No Self- | will execute a | |
Test | |||
UPS ID | UPS_IDEN | Up to eight characters to | Use this field to uniquely identify the |
define the UPS. | UPS for network management | ||
purposes. | |||
Date of Last Battery | Manufacture | Date of Battery | Reset this date on battery |
Replacement | Date | Replacement | replacement. |
Minimum Capacity Before | 0 percent | 15, 50, 90 percent | The UPS will charge its batteries to |
Return from Shutdown | the specified percentage before return | ||
from a shutdown. | |||
Sensitivity | Normal | Reduced, Low | Set lower than normal sensitivity to |
avoid lowered battery capacity and | |||
service life in situations where the | |||
load can tolerate minor power | |||
disturbances. | |||
Duration of Low Battery | 2 minutes | 5, 7, 10 minutes | Sets the time before shutdown at |
Warning | which the UPS issues a low battery | ||
warning. Set higher than the default | |||
only if the OS needs the time for | |||
graceful shutdown. | |||
Alarm Delay After Line Fail | 5 second delay | 30 second delay, At Low | To avoid alarms for minor power |
Battery Condition, No | glitches, set the alarm delay. | ||
Alarm | |||
Shutdown Delay | 20 seconds | 180, 300, 600 seconds | Sets the interval between when the |
UPS receives a shutdown command | |||
and when shutdown occurs. | |||
Synchronized | 0 seconds | 60, 180, 300 seconds | To avoid branch circuit overload, |
the UPS will wait the specified time | |||
after the return of utility power before | |||
Output Voltage | 230 Vac | 220, 225, 240 VAC | Sets the output voltage for |
operation. | |||
High Transfer Point | 253 Vac | 264, 271, 280 VAC | To avoid unnecessary battery usage, |
set the High Transfer Point higher if | |||
the utility voltage is chronically high | |||
and the load is known to work well | |||
under this condition. | |||
Low Transfer Point | 196 Vac | 188, 204, 208 VAC | Set the Low Transfer Point lower if |
the utility voltage is chronically low | |||
and the load can tolerate this | |||
condition. |
Service
If the UPS requires service do not return it to the dealer!
Follow these steps:
1.Use the Troubleshooting section of theQuick Reference Guide to eliminate common problems.
2.Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem!
3.If the problem persists, call customer service or visit the APC Internet Website (www.apcc.com).
•Note the model number of the UPS, the serial number, and the date purchased. A technician will ask you to describe the problem and try to solve it over the phone, if possible. If this is not possible the technician will issue a Return Merchandise Authorization Number (RMA#).
•If the UPS is under warranty, repairs are free. If not, there is a repair charge.
4.Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.
•Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.
•Include a letter with your name, RMA#, address, copy of the sales receipt, description of the trouble, your daytime phone number, and a check (if necessary).
5.Mark the RMA# on the outside of the package
6.Return the UPS by insured, prepaid carrier to the address given to you by Customer Service.
North & Latin America | Europe |
APC | APC |
132 Fairgrounds Road | Ballybritt Business Park |
West Kingston, Rhode Island 02892 USA | Galway, Ireland |
Internet: http://www.apcc.com | |
Apc Smart Ups 1500 User's Manual
Regulatory Agency Approvals
B
N 3 9 M E6 1
Apc Smart Ups 2200 Lcd Manual
Specifications
Apc Smart-ups 2200 Manual Download
450 VA | 700 VA | 1000 VA | 1400 VA | 2200 VA | 3000 VA | ||||
Acceptable input voltage | 0 - 325 VAC | ||||||||
Output voltage | |||||||||
Input Protection | Resettable circuit breaker | ||||||||
Frequency limits | 50 or 60 Hz, ±5% | ||||||||
Transfer time | 2 ms typical, 4 ms maximum | ||||||||
Maximum load Free titler pro 5 download. NewBlueFX Titler Pro 5 is an effectual pc software for producing two-dimensional and three-dimensional text in your movies. As it had been specifically made becoming placed to the movie, the task is quite confident with most of the needed features. Titler Pro 7 is the industry standard in titling software for video editors. Deliver exceptional production value with stunning 3D animated titles and motion graphics, without sacrificing productivity. Titler Pro 7 integrates with all of today's leading NLEs; use it as plugin within your favorite editing software, or as a standalone application. Titler Pro 5 License Serial Key Features: NewBlueFX Titler Pro 5 Ultimate Crack Plus Serial Key Free Download allows you to quickly create a title and then take it to a new level with text extrusion, custom lighting and preset animations. Besides, you can choose from over 200 built-in styles and templates for an immediate result. | 450 VA | 700 VA | 1000 VA | 1400 VA | 2200 VA | 3000 VA | |||
280 W | 450 W | 670 W | 950 W | 1600 W Differential equations solutions. | 2250 W | ||||
220, 225, 230, or 240 VAC | |||||||||
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout. | |||||||||
Protection | Overcurrent and | ||||||||
Noise Filter | Normal and common mode EMI/RFI suppression, 100 kHz to 10 MHz | ||||||||
Battery type | Spill proof, maintenance free, sealed | ||||||||
Typical battery life | 3 to 6 years, depending on number of discharge cycles and ambient temperature | ||||||||
Typical recharge time | 2 to 5 hours from total discharge | ||||||||
Operating temperature | 0 to +40 ºC (+32 to +104 ºF) | ||||||||
Storage temperature | |||||||||
Operating and storage relative | 0 to 95%, | ||||||||
humidity | |||||||||
Operating elevation | 0 to +3,000 m (0 to +10,000 ft) | ||||||||
Storage elevation | 0 to +15,000 m (0 to +50,000 ft) | ||||||||
Electromagnetic immunity | IEC | ||||||||
Audible noise in dBA at 1 m (3 ft) | <41 | <42 | <45 | <53 | |||||
Size (H x W x D) | 15.8 x 13.7 x 35.8 cm | 21.6 x 17 x 43.9 cm (8.5 x | 43.2 x 19.6 x 54.6 cm (17.0 | ||||||
(6.2 x 5.4 x 14.1 in.) | 6.7 x 17.3 in.) | x 7.7 x 21.5 in.) | |||||||
Weight - net (shipping) | 10.5 | 13.1 | 18.8 | 24.1 (26.1) | 51 (60.8) kg | 55.8 (64.4) | |||
(11.8) | (14.5) | (20.8) kg | kg | 112 (134) | kg | ||||
kg | kg | 41.5 (46) | 53 (58) lb. | lb. | 123 (142) | ||||
23.2 | 29 (32) | lb. | lb. | ||||||
(26) lb. | lb. | ||||||||
Safety approvals | GS licensed by VDE to EN 50091 and 60950 | ||||||||
EMC verification | CISPR 22 Class A |